A320 electrical failures

Electrical bus failures

FCOM DSC-24-10-30-30 P 1–4 · PRO-ABN-ELEC P 9–19, 40–55, 80–95, 113–114

How the network reconfigures

One generator lost
The APU generator takes over if available, otherwise the other engine generator feeds both sides; part of the galley load is shed
AC BUS 1 lost
AC BUS 2 can feed AC ESS, and the ESS TR feeds DC ESS, through AC ESS FEED; DC BUS 2 feeds DC BUS 1 and DC BAT after 5 s
One TR lost
The other TR replaces it, and the ESS TR supplies DC ESS
TR 1 and TR 2 lost
DC BUS 1, DC BUS 2 and DC BAT are lost; the ESS TR keeps DC ESS

ELEC GEN 1(2) FAULT

Trigger
Protection trip by the generator control unit, or line contactor open with the GEN pushbutton on
Actions
GEN off then on; if that fails, GEN off
With the APU generator
Nothing else is lost
Without it
Galleys shed; CAT 3 SINGLE ONLY

ELEC AC BUS 1 FAULT

First effect
AC ESS and DC ESS go with it until AC ESS FEED is on ALTN; automatic on aircraft with auto switching
Actions
BLOWER OVRD
Secondary failures
AVNCS VENT, HYD, FUEL, F/CTL
Lost
Blue hydraulics, spoiler 3, ADR 3, RA 1, left windshield and window heat, tank pumps 1, BRK SYS 1, DMC 3, TCAS, GPWS, reverser 1
Landing
CAT 2 ONLY, slats slow, landing distance procedure, fuel consumption increased

ELEC AC ESS BUS FAULT

Actions
AC ESS FEED ALTN, so AC BUS 2 supplies the bus; ATC/XPDR SYS 2
Lost until recovered
Captain's PFD and ND, upper ECAM display, ADR 1, FWC 1, SDAC 1, DMC 1, MCDU 1, VOR 1, DME 1, GPWS, yaw damper 1, rudder trim 1, CVR, passenger oxygen masks
Landing
CAT 2 inoperative

ELEC DC BUS 2 FAULT

Actions
AIR DATA SWTG F/O 3 if ADR 3 is available; BARO REF check, because one FCU channel is lost
Secondary failures
CAB PRESS, FUEL, WHEEL, F/CTL
Lost
Spoilers 1, 2 and 5, ELAC 2, SEC 2 and 3, FAC 2, FMGC 2, AP 2, FCU 2, VHF 2, tank pumps 2, autobrake, LGCIU 2, BRK SYS 2, reverser 2, CAB PR 2, right window heat
Landing
CAT 3 SINGLE ONLY, slats and flaps slow, engine 2 at approach idle only, speeds from FAC 1, landing distance procedure

ELEC DC ESS BUS FAULT

Actions
VHF 2 or 3 in use; BARO REF check; GPWS off; GALY & CAB off; avoid icing conditions
Secondary failures
CAB PRESS, HYD, F/CTL
Lost
Blue hydraulics, spoiler 3, VHF 1, AP 1, FCU 1, FAC 1, tank pumps 1, CAB PR 1, wing anti-ice, alternate braking, ECAM control panel, brake pressure indicator
Landing
CAT 3 SINGLE ONLY, slats and flaps slow, engine 1 at approach idle only, speeds from FAC 2, landing distance procedure
With DC BUS 2 also lost
Gravity gear extension; no aural alerts or automatic callouts; transponder 1 only
  • Each alert can come from a sub-bus failure, so only part of its list may be lost.
  • STATUS gives the landing capability: compare it with the approach planned.
  • With DC ESS lost, the engines are shut down on the ground with the ENG FIRE pushbuttons on some aircraft, because the HP fuel valves no longer close from the master switches.
  • The network and its ECAM page are on the electrical system page.

With BUS TIE in AUTO and the APU generator unavailable, what happens if GEN 1 becomes inoperative?

Emergency electrical configuration

FCOM DSC-24-10-30-30 P 5 · PRO-ABN-ELEC P 100–109 · FCTM PR-AEP-ELEC

Trigger
AC BUS 1 and AC BUS 2 both lost
Power
Above 100 kt the RAT extends and pressurises blue hydraulics, which drive the emergency generator: AC ESS, and DC ESS through the ESS TR
First 8 s
The batteries carry the network while the RAT extends and the generator couples
Speed
MIN RAT SPEED 140 kt; maximum 320 kt
Actions
LAND ASAP; GEN 1 and 2 off then on, then BUS TIE off and again; EMER ELEC PWR MAN ON if the generator is not on line; ENG MODE SEL IGN; FAC 1 off then on; BLOWER and EXTRACT OVRD
Radios
VHF 1, HF 1 and ATC 1 only
Fuel
Gravity feeding: avoid negative g
APU
Start inhibited for 45 s; then possible below FL 250
Flight controls
Alternate law, protections lost; direct law in pitch and roll at gear extension
Lost
AP 1 and 2, A/THR, FMGC 2, reversers, antiskid, nosewheel steering, RA 1 and 2, automatic callouts, spoilers 1, 2 and 5, ADR 2 and 3, IR 2 and 3, fuel pumps, CAT 2
Approach
Flap lever 3; VREF + 15 kt, or + 10 kt on older standards, and never below 140 kt; slats and flaps slow
Braking
No antiskid: 1,000 psi at most
  • The RAT drives the generator down to about 125 kt, but may not hold it through the flare.
  • Only PFD 1 is left, so the captain flies.
  • FAC 1 off then on brings the rudder trim back, with no indication.
  • FMGC 1 drops out for a moment and comes back through MCDU MENU.
  • If the RAT stalls, the batteries and static inverter take over and the AC and DC SHED ESS buses are shed.
  • On the ground the batteries connect to DC BAT below 100 kt; below 50 kt AC ESS is shed and every display goes blank.
  • The standby airspeed probe is not heated: if it disagrees with PFD 1, PFD 1 is used.

What happens when AC BUS 1 and AC BUS 2 are both lost in flight above 100 kt?

Display failures

FCOM DSC-31-05-60 P 1–2 · PRO-ABN-EIS P 1–6

PFD unit fails
The PFD image moves to the ND unit by itself; PFD/ND XFR swaps the two
ND unit fails
PFD/ND XFR puts the ND image on the PFD unit
Upper ECAM unit fails
The E/WD moves to the lower unit by itself
One ECAM unit left
System or status page through ECAM/ND XFR on an ND, or by holding its key, for 3 minutes at most
Both ECAM units fail
ECAM/ND XFR puts the E/WD on an ND
Unit blank or distorted
Its brightness knob off then on; if it stays failed, consider ECAM/ND XFR or PFD/ND XFR
INVALID DISPLAY UNIT
Wait at least 40 s for the unit to recover
INVALID DATA on some units
Consider EIS DMC switching
EIS DMC 1(2) FAULT
EIS DMC to CAPT 3 or F/O 3: DMC 3 replaces the failed one
Units flashing on one side
That side's generator off; if the flashing goes on, generator back on
  • Flashing units, a flashing MCDU or a flight control law that comes and goes point to short power interruptions.
  • Captain's units or MCDU 1: GEN 1. First officer's units, lower ECAM or MCDU 2: GEN 2.
  • If the flashing stops, the generator stays off for the flight: check the rudder trim against the sideslip index and consider the APU.
  • An AC ESS BUS failure takes the captain's PFD and ND and the upper ECAM unit together.
  • More on the E/WD and its messages on the ECAM messages page.

If a PFD display unit fails, how is the PFD image transferred to the adjacent ND display unit?

Practise every system

Free includes five questions in each system with no account or payment card required. Premium costs CHF 19/month and unlocks all 2,039 A320Q questions across 20 categories in Quick, Exam and Streak modes.

Compare Free and Premium

Questions about A320 electrical failures

What is the minimum RAT speed in emergency electrical configuration?

140 kt. The RAT can drive the emergency generator down to about 125 kt, but may not keep it on line through the flare at that speed. The approach speed is never set below 140 kt.